This article contains affiliate links. If you buy through our links, we may earn a commission at no extra cost to you. See our full disclosure for details.

Electrical work is the most critical and most frequently botched aspect of sauna heater installation. An incorrectly wired heater is a fire hazard, a code violation, and an insurance liability. This guide covers the electrical requirements for every common sauna heater configuration, from small 3kW units on standard household circuits to 18kW commercial units on heavy three-phase feeds.

What Electrical Concepts Matter for Sauna Heaters?

Three values determine every sauna heater electrical decision: power (kW), voltage (230V single-phase or 400V three-phase), and current (amps). Understanding how these relate lets you size breakers, wire gauge, and determine whether you need a panel upgrade.

Before diving into specifications, three values determine every electrical installation decision:

Power (kW)

The heater’s rated power output in kilowatts. This is fixed by the heater model. A 9kW heater draws 9kW at full power regardless of how it is wired.

Voltage (V)

The electrical supply voltage. Two configurations are standard for sauna heaters:

  • 230V single-phase: Standard residential power in North America and most of the world. Two conductors (line and neutral) plus ground.
  • 400V three-phase: Standard in European residential and North American commercial/industrial. Three conductors (three phase lines) plus neutral plus ground. Standard residential supply in Finland, Sweden, Norway, and much of continental Europe.

Current (Amps)

The current draw, calculated from power and voltage:

Single-phase: Amps = Watts / Volts Three-phase: Amps = Watts / (Volts x 1.732)

Example: A 9kW (9,000W) heater:

  • On 230V single-phase: 9,000 / 230 = 39.1A
  • On 400V three-phase: 9,000 / (400 x 1.732) = 13.0A per phase

This is why three-phase power is preferred for larger heaters: the same 9kW load draws 39A on single-phase but only 13A per phase on three-phase. Lower current means smaller wire, smaller breakers, and less stress on the electrical system.

What Are the 230V Single-Phase Requirements for a Sauna Heater?

A 230V single-phase circuit handles sauna heaters up to approximately 8kW. A typical 6kW heater draws 26A and requires a 32A breaker with 4.0mm2 (10 AWG) wire on a dedicated circuit. Beyond 8kW, the current draw becomes impractically high for single-phase.

Single-phase is the practical option for heaters up to approximately 8kW in most residential installations. Beyond 8kW, the current draw on single-phase becomes impractically high (40A+ breakers, heavy wire gauge).

Specification Table: 230V Single-Phase

Heater PowerCurrent DrawBreaker SizeMin Wire Gauge (mm2)Min Wire Gauge (AWG)Max Wire Run (m)
3.0kW13.0A16A2.51425
3.6kW15.7A20A2.51420
4.5kW19.6A25A4.01225
6.0kW26.1A32A4.01020
7.0kW30.4A40A6.01020
8.0kW34.8A40A6.0815
9.0kW39.1A50A10.0815

Key Notes for Single-Phase

Breaker sizing: The breaker must be rated above the continuous current draw but sized according to the wire gauge capacity. The values in the table follow NEC (National Electrical Code) guidelines. Local codes may vary. Always follow the more restrictive standard.

Wire gauge: These are minimum values for the stated maximum wire run distances. For longer runs, step up one wire gauge to compensate for voltage drop. A 1-2% voltage drop is acceptable. Above 3%, heater performance degrades noticeably (slower heat-up, lower maximum temperature).

Voltage drop calculation:

Voltage drop (%) = (2 x Length x Current x Resistivity) / (Cross-sectional area x Voltage) x 100

For copper wire at 75C:

  • 2.5mm2: 7.41 milliohm/m
  • 4.0mm2: 4.61 milliohm/m
  • 6.0mm2: 3.08 milliohm/m
  • 10.0mm2: 1.83 milliohm/m

Example: 8kW heater (34.8A) on 6.0mm2 wire at 20m run:

  • Voltage drop = (2 x 20 x 34.8 x 3.08) / (1 x 230) x 1000 = 4,289 / 230,000 = 1.86%
  • This is within the acceptable 3% limit.

At 30m run:

  • Voltage drop = (2 x 30 x 34.8 x 3.08) / (1 x 230) x 1000 = 6,434 / 230,000 = 2.80%
  • Still within 3%, but at the edge. For 30m runs, step up to 10mm2 wire.

Dedicated Circuit

Every sauna heater requires a dedicated circuit. No shared loads. No other outlets, lights, or appliances on the same circuit. This isn’t optional. It is a code requirement in virtually all jurisdictions.

The only exception: some heater models allow the sauna room light (typically under 100W) to be wired through the heater’s internal junction box. Check the manufacturer’s wiring diagram for your specific model.

When Does a Sauna Heater Need 400V Three-Phase Power?

Any sauna heater above 8kW typically requires 400V three-phase power. Three-phase distributes the load across three conductors, so a 9kW heater draws only 13A per phase instead of 39A on single-phase. Allowing smaller wire gauges and breakers.

Three-phase power is the standard for heaters above 8kW and is required for most heaters above 10kW. Three-phase distributes the current load across three conductors, reducing the current per conductor and allowing smaller wire gauges.

Specification Table: 400V Three-Phase

Heater PowerCurrent Draw (per phase)Breaker SizeMin Wire Gauge (mm2)Min Wire Gauge (AWG)Max Wire Run (m)
6.0kW8.7A10A1.51630
8.0kW11.5A16A2.51430
9.0kW13.0A16A2.51425
10.5kW15.2A20A2.51220
11.0kW15.9A20A2.51220
12.0kW17.3A20A4.01225
15.0kW21.7A25A4.01020
18.0kW26.0A32A6.01020

Conductor Count

Three-phase sauna circuits use 5-conductor cable:

  1. Phase L1
  2. Phase L2
  3. Phase L3
  4. Neutral (N)
  5. Ground/Earth (PE)

Some heater models don’t use the neutral conductor (they are “delta” connected rather than “star/wye” connected). In this case, 4-conductor cable is sufficient. Check the heater’s wiring diagram. When in doubt, run 5-conductor cable. The cost difference is minimal, and having the neutral available provides flexibility if you change heaters later.

Three-Phase Availability

Europe (most countries): 400V three-phase is standard residential supply. Your distribution panel likely already has three-phase capacity. Connecting a sauna heater circuit is straightforward.

North America (US, Canada): Standard residential supply is 240V split-phase (not true three-phase). To get 400V three-phase, you need either:

  1. Utility service upgrade: The utility installs a three-phase transformer and service entrance. Cost: $1,500-5,000 depending on distance and local utility pricing.
  2. Phase converter: A rotary or electronic phase converter generates the third phase from single-phase supply. Cost: $800-2,000 for the converter, plus installation. Phase converters work but add complexity and a potential failure point.
  3. Different heater model: Some manufacturers offer 240V single-phase versions of their three-phase models for the North American market. These use heavier wire but avoid the three-phase requirement.

Australia, New Zealand: 415V three-phase is standard residential in many areas. Similar to Europe, three-phase heater connections are straightforward.

How Many Amps Does a Sauna Heater Draw?

Divide watts by volts for single-phase, or by volts times 1.732 for three-phase. A 6kW heater draws 26A on 230V single-phase. A 9kW heater draws 13A per phase on 400V three-phase. The exact amperage depends on your actual supply voltage.

To calculate the amp draw for any sauna heater:

Single-Phase

Amps = Power (W) / Voltage (V)

Power208V220V230V240V
4.5kW21.6A20.5A19.6A18.8A
6.0kW28.8A27.3A26.1A25.0A
8.0kW38.5A36.4A34.8A33.3A
9.0kW43.3A40.9A39.1A37.5A

Note that US residential voltage varies between 208V (in some apartment buildings) and 240V. The actual voltage at your panel affects current draw. At 208V, a given heater draws more current than at 240V, which may require a larger breaker or heavier wire. Verify your actual supply voltage before sizing the circuit.

Three-Phase

Amps per phase = Power (W) / (Voltage (V) x 1.732)

Power380V400V415V
9.0kW13.7A13.0A12.5A
10.5kW16.0A15.2A14.6A
12.0kW18.2A17.3A16.7A
15.0kW22.8A21.7A20.9A
18.0kW27.3A26.0A25.0A

Do I Need an Electrician to Wire a Sauna Heater?

Yes for all three-phase installations and for any single-phase circuit above 20A. A 3-4.5kW heater on a 16-20A circuit is technically within DIY capability, but most jurisdictions require permits for any new circuit, and insurance may not cover self-installed wiring.

Always for Three-Phase

Three-phase wiring involves three energized conductors at 400V. A wiring error can destroy the heater, trip the main breaker, or create a phase-to-phase short circuit capable of delivering extremely high fault currents. This isn’t a DIY project. Hire a licensed electrician.

Almost Always for Single-Phase Above 20A

In most jurisdictions, circuits above 20A require a permit and licensed electrician. Even where permits aren’t strictly enforced, the liability implications of a self-installed 40A+ circuit that causes a fire are severe.

Potentially DIY for Small Single-Phase

A 3-4.5kW heater on a 16-20A circuit is within the technical capability of an experienced homeowner with electrical knowledge. However:

  • Check local codes. Many jurisdictions require permits for any new circuit, regardless of amperage.
  • Your homeowner’s insurance may not cover damage from a self-installed electrical circuit.
  • If you are asking whether you can do this yourself, the answer is probably that you should hire an electrician.

Does a Sauna Heater Need GFCI or RCD Protection?

In North America, NEC 680.44 generally requires GFCI protection for sauna heater circuits rated 60A or less, though a hardwired installation exception may apply. In Europe, RCD requirements vary by country, and Finnish practice typically protects the control circuit only to avoid nuisance tripping.

North America (NEC)

The National Electrical Code (NEC) has specific requirements for sauna heater circuits:

  • NEC 680.44: Equipment in sauna rooms must be connected to a circuit protected by a ground-fault circuit interrupter (GFCI) if the circuit is rated 60A or less and 150V to ground or less. For 240V circuits (120V to ground per leg), GFCI protection is required.
  • Exception: Some jurisdictions exempt dedicated heater circuits from GFCI requirements if the heater is hardwired (not plug-connected) and installed per manufacturer instructions.

Practical reality: GFCI breakers on high-amperage sauna circuits are prone to nuisance tripping, particularly during the rapid current draw changes that occur as heater elements cycle on and off. Many electricians install standard breakers and document the heater manufacturer’s installation instructions as the basis for the GFCI exception.

Discuss GFCI requirements with your electrician. The correct approach depends on your local code adoption and inspector interpretation.

Europe (IEC)

European installations typically require RCD (residual current device) protection with 30mA sensitivity on all socket outlet circuits and circuits supplying equipment in wet areas. A dedicated sauna heater circuit hardwired through a contactor or control unit may or may not require RCD protection depending on the national wiring regulations of your country.

In Finland (where most sauna heaters are designed), sauna heater circuits are typically installed without RCD protection on the heater circuit itself, with RCD protection on the control circuit only. This avoids nuisance tripping while maintaining ground fault protection on the low-voltage control wiring.

How Far Can You Run Wire to a Sauna Heater?

Maximum wire run depends on wire gauge and current draw, limited by a 3% voltage drop threshold. For a typical 35A single-phase circuit on 6.0mm2 wire, the maximum run is about 41 meters. Longer runs to detached sauna buildings require stepping up the wire gauge.

Wire run distance (the total length of cable from the electrical panel to the heater connection point) affects voltage drop. Longer runs require heavier wire to maintain adequate voltage at the heater.

Maximum Run Distances (3% voltage drop limit)

Wire Gauge (mm2)Single-Phase 230V, 20ASingle-Phase 230V, 35AThree-Phase 400V, 16A
1.518m,25m
2.530m17m42m
4.048m27m67m
6.072m41m100m
10.0120m69m167m

For most residential installations, wire runs are under 20m, and the minimum wire gauges listed in the heater specification tables are sufficient. For detached saunas, outbuilding installations, or basement-to-attic runs, calculate the actual wire run length and verify the voltage drop is within limits.

Underground Runs

If your sauna is in a detached building, the wire run from your main panel likely includes an underground segment. Underground wire must be:

  • Direct burial rated (UF cable in the US) or installed in conduit
  • Buried to code depth: 24 inches minimum for UF cable, 18 inches for cable in rigid conduit, 12 inches for cable in PVC conduit (NEC requirements, and local codes may vary)
  • Protected at entry and exit points with conduit risers

Underground runs add to the total wire length for voltage drop calculations. A 15m house run plus a 20m underground run is a 35m total run.

Does My Electrical Panel Have Capacity for a Sauna Heater?

Subtract your existing breaker load from the main breaker rating. If the remaining capacity exceeds your heater’s breaker requirement, you are fine. If not, a panel upgrade ($1,500-3,000 for 100A to 200A) is required before installing the sauna circuit.

Before adding a sauna heater circuit, verify your electrical panel has sufficient capacity.

How to Check

  1. Find your panel’s main breaker rating (typically 100A, 150A, or 200A for residential panels).
  2. Sum the amperage of all existing breaker slots in use.
  3. Subtract from the main breaker rating to find available capacity.
  4. Verify the available capacity exceeds your heater circuit’s breaker requirement.

Example: A 200A panel with 140A of existing breaker capacity has 60A available. A 40A sauna circuit is within capacity.

Example: A 100A panel with 80A of existing loads doesn’t have capacity for a 40A sauna circuit. Panel upgrade required.

Panel Upgrade Costs

UpgradeTypical Cost (US)
100A to 200A panel upgrade$1,500-3,000
Add sub-panel (for detached building)$800-1,500
Three-phase service installation$1,500-5,000

These costs are in addition to the sauna heater circuit installation cost.

How Do You Wire a Sauna Heater Control Unit?

The wiring path runs from panel to control unit to heater, using two separate full-amperage cable runs. The control unit mounts outside the sauna in a dry location (40C max ambient), and a low-voltage sensor cable runs from it to a temperature sensor inside the sauna room.

Most sauna heaters above 6kW use an external control unit (contactor/controller) mounted outside the sauna room. The wiring path is:

Panel –> Control Unit –> Heater

Two separate cable runs are required:

  1. Panel to control unit: Full-amperage rated cable matching the heater’s power requirements (use the specifications tables above).
  2. Control unit to heater: Heater cable, also full-amperage rated. Length determined by heater manufacturer (typically 3-5m included with the heater, extensions available).

Additionally, a sensor cable runs from the control unit’s temperature sensor to a mounting point inside the sauna room, usually on the ceiling or high on the wall above the heater. This is low-voltage signal wire (typically 2-conductor, 0.5-1.0mm2) and doesn’t require the same heavy gauge as the power cables.

The control unit must be mounted in a dry location outside the sauna room. It can’t be inside the sauna. The ambient temperature rating of most control units is 40C maximum.

How Much Does Sauna Heater Electrical Installation Cost?

A simple 230V 20A circuit costs $200-400, a dedicated 230V 40A circuit runs $300-500, and a 400V three-phase circuit with existing panel costs $400-600. If you need new three-phase service, expect $2,000-5,600 total.

ScenarioEstimated Cost (US)
Simple run from panel to adjacent room, 230V 20A$200-400
Dedicated 230V 40A circuit, 10-15m run$300-500
Dedicated 400V 3-phase circuit, existing 3-phase panel$400-600
400V circuit with new 3-phase service$2,000-5,600
Underground run to detached sauna building$500-1,200 (in addition to circuit cost)
Panel upgrade + sauna circuit$2,000-3,500

These are labor + materials estimates for licensed electrician work in the US (2026 pricing). Costs vary significantly by region, with urban areas typically 20-40% higher than rural areas.

What Should I Prepare Before My Electrician Arrives?

Have seven items ready: the heater model and kW rating, required voltage, manufacturer wiring diagram, measured wire run distance, control unit location, sensor cable routing plan, and confirmed panel capacity. This preparation saves time and money on installation day.

Before your electrician arrives, have the following information ready:

  1. Heater model and power rating (kW)
  2. Required voltage (230V single-phase or 400V three-phase)
  3. Manufacturer’s wiring diagram (included with the heater or available from manufacturer website)
  4. Wire run distance (measured from panel to heater location)
  5. Control unit location (where the controller will be mounted outside the sauna)
  6. Sensor cable routing (from control unit to inside the sauna room)
  7. Panel capacity (verify available amperage before the electrician arrives)

Providing this information upfront saves your electrician’s time and your money. Most electricians can complete a sauna heater circuit installation in 3-6 hours if the information is prepared and the routing is clear.

Bottom Line

Electrical installation is the one aspect of a sauna build where cutting corners has real safety consequences. Size the breaker and wire gauge to the heater’s actual current draw, not to what you hope it might be. Account for wire run distance in your voltage drop calculations. Hire a licensed electrician for any circuit above 20A, and for all three-phase work. The $300-600 cost of proper electrical installation is trivial compared to the cost of a house fire or an insurance claim denied due to non-code wiring. Get it right the first time.